Siemens QRA10 Burner Flame Sensors & Detectors For Oil & Gas Industrial Burners

  • Home
  • Products
  • Siemens QRA10 Burner Flame Sensors & Detectors For Oil & Gas Industrial Burners
Industrial Grade
Thumb

Siemens QRA10 Burner Flame Sensors & Detectors For Oil & Gas Industrial Burners

Siemens QRA10 Burner Flame Sensor & Detector is a high-performance UV flame detector designed for monitoring gas and oil burner flames, ensuring reliable flame supervision and safe operation in industrial combustion systems.

High Efficiency
Durable Build
Tested Standards
B2B Support
Download Specs

Description

Product Overview

The Siemens QRA10 Flame Sensor & Detector is an ultraviolet (UV) flame detector used for monitoring gas flames and yellow or blue oil flames in industrial burner systems. It detects the UV radiation emitted by a flame and sends a signal to the burner control system to confirm safe burner operation.

The detector is designed for intermittent burner operation, making it suitable for combustion systems that shut down periodically, such as industrial boilers and process burners.

The QRA10 features a robust die-cast aluminum housing, which protects the internal UV cell from harsh industrial environments. It includes a mounting coupling for installation on a viewing tube or burner housing and provides a connection for cooling air to prevent overheating and soot accumulation on the lens.

This detector is widely used with Siemens burner control units such as LFL, LAL, LFE, LME, and LMV series controllers, making it a versatile solution for flame monitoring in industrial combustion equipment.


Key Features

Designed for oil and gas industrial burners

High-sensitivity ultraviolet (UV) flame detection

Detects UV radiation emitted by gas and oil flames

Suitable for intermittent burner operation

Rugged die-cast aluminum housing for industrial environments

Connection for cooling air to maintain sensor performance

Compatible with multiple Siemens burner controllers

Replaceable UV sensor tube for easy maintenance

Reliable flame supervision for safe burner operation

Applications

  • Industrial gas burners

  • Industrial oil burners

  • Dual-fuel combustion systems

  • Steam boilers and hot water boilers

  • Industrial furnaces and ovens

  • Thermal processing equipment

  • Process heating systems

Why Choose Siemens QRA10 Flame Detector?

Trusted Siemens combustion safety technology

Highly accurate UV flame detection

Reliable flame monitoring for industrial burners

Durable design for harsh industrial environments

Compatible with many Siemens burner control systems

Long service life with replaceable UV cell

Technical Description

The Siemens QRA10 Flame Detector operates using an ultraviolet (UV) sensor that detects radiation emitted by burner flames in the wavelength range of approximately 190–270 nm. When the detector senses sufficient UV radiation, it generates an electrical signal indicating the presence of a flame.

This signal is transmitted to the burner control unit, which verifies flame presence during ignition and burner operation. If the flame signal disappears during operation, the burner control system initiates a safety shutdown to prevent unsafe combustion conditions.

The detector is designed with a 1-inch mounting coupling and bayonet connection, allowing easy installation on a burner viewing tube or combustion chamber inspection port. A cooling air connection helps maintain the internal temperature of the UV cell and prevents soot buildup on the detector window.

The internal UV cell typically has a service life of approximately 10,000 operating hours, after which replacement of the UV tube is recommended to maintain accurate flame detection.


Technical Specifications

Specification

Details

Brand

Siemens

Model

QRA10

Product Type

UV Flame Sensor / Flame Detector

Burner Type

Oil & Gas Industrial Burners

Detection Method

Ultraviolet (UV) Flame Detection

Spectral Sensitivity

Approx. 190 – 270 nm

Flame Types

Gas flames, yellow or blue oil flames

Operation Mode

Intermittent operation

Housing Material

Die-cast aluminum

Protection Class

IP54

UV Cell Life

Approx. 10,000 hours

Mounting

1-inch mounting coupling / viewing tube

Operating Temperature

−20°C to +60°C

Weight

Approx. 0.74 kg

Compatible Controllers

LFL, LAL, LFE, LME, LMV series

Typical Applications

Industrial burners, boilers, furnaces

Email Us Call Us WhatsApp